Water to Water Ground Source Heat Pump

Water to Water Ground Source Heat Pump

  • Main Features:
    • R32 or R410a
    • 3.5 kw to 300 kw or bigger
    • Function: Hot Water/Cold water/heating/cooling
    • Centralized Control
    • Copland/Danfoss Compressor
    • Electric expansion valve
    • High Efficient heat exchanger or tube in Shell heat exchanger
    • Customized Design as customers’ projects
  • Applications:
    Residential and commercial hot water, heating/cooling: House, Apartment, Vila, Hotel, Hospital, Spa, Holiday Center, and so on.

Core Strengths

18 years experience - FANTASTIC company has manufactured over 35,000 water to water heat pumps worldwide

Affordability - Save energy & high performance  - As the high COP of FANTASTIC  geothermal heat pump, it can heat the water for about 30% of the cost of heating with gas and  75% of electric water heater, High COP means more energy saving.
Ex. $1 input - $ 4.6 of energy output at COP of 4.6

Long life with famous brand high-quality components - CAREL controller and CAREL expansion valve for option, Copland or Panasonic compressor, SWEP plate heat exchanger, and WILO water pump, and so on. All the heat pumps equipped with famous international brand components, and we also can manufacture the casing with stainless steel, and much experience on titanium heat exchanger heat pump for someplace where water quality is pool or water requirement is special.

Wide models range - we can design and make from resident to commercial ground source heat pump up to 350 Kw or bigger as your actual pool situation.

 

Water-to-water-(Ground-source)heat-pump-8-min.jpg

 
  • Wide Heating Capacity Range

  • Lower Running Cost Than Traditional Heat Pump

  • Using Copper-Nickel Heat Exchanger for Option

  • Intelligent Curve Economic Control Mode

  • Centralized Control

  • Super-heat Management

Wide Heating Capacity Range

The heating capacity of FANTASTIC Air to heat pump is up to 300 Kw or bigger. Suitable for different size of project demand, no matter for household or commercial using. Customized Design for different customers’ projects.

Water-to-water--Ground-source-heat-pump-2-min.jpg

Lower Running Cost Than Traditional Heat Pump

FANTASTIC heat pump has precise energy stage settings ensures the working unit to achieve the desired energy saving efficient. Heat pump will change compressor using quantity as the real heat required by water inlet temperature. When need higher heating load, it will use full compressor quantity, when water temperature close to target set temperature, it need lower heating load, then will off some compressor and just use the compressor quantity as the real heat load.

Water-to-water--Ground-source-heat-pump-9.jpg

Using Copper-Nickel Heat Exchanger for Option

FANTASTIC water to water heat pump would be with copper-nickel heat exchanger for option, super anti-corrosion and no easy to go rust, improves the heat transfer ability and reducing water film, and improving efficiency.

Water-to-water-(Ground-source)heat-pump-3-min.jpg

Intelligent Curve Economic Control Mode

Intelligent working mode with winter Heating Curve,according to the change of water temperature,the heat pump will calculate and supply the most suitable water temperature automatically to save much energy and provide more comfortable and enough heating /cooling.

Water-to-water-(Ground-source)heat-pump-5-min.jpg

Centralized Control

FANTSTIC controller can control up to 16 units of heat pump at the same time by one controller comes equipped with centralized control that makes temperature adjustment and failure review much easier and more practical. By incorporating the master-slave control into the design, the whole units can work together with higher efficiency without interfered by any failure of the slave unit during operation, and can be choose all heat pump work at the same time or only some of heat pumps work according the actual demand automatically, more energy-saving.

Water-to-water--Ground-source-heat-pump-1-min.jpg

Super-heat Management

FANTASTIC heat pump increases Heating capacity and extend the Operation life by TEV, and increases COP and limit the discharge temperature under safe level by EEV, and less the defrosting time to make heat pump put more time on heating and more energy-saving.

Water-to-water-(Ground-source)heat-pump-6-min.jpg
  • PRAMETER

Water source heat pump (Heating, cooling, hot water)
Model   FWWHCD030 FWWHCD0503 FWWHCD0603 FWWHC10603 FWWHCD1203 FWWHCD1403 FWWHCD2003 FWWHCD2503 FWWHCD3003 FWWHCD3603 FWWHCD4003 FWWHCD5003 FWWHCD0603 FWWHCD10003
Heating capactiy① KW 9.6 16.0 19.2 32.0 38.4 44.8 64.0 80.0 96.0 115.2 128.0 168.0 192.0 320.0
BTU/h 32800 54600 65500 109200 131000 152900 218400 273000 327600 393100 436700 573200 655100 1091800
COP① W/W 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
Input power (Heating)① KW 1.78 2.96 3.56 5.93 7.11 8.30 11.85 14.81 17.78 21.33 23.70 31.11 35.56 59.26
Input current (Heating)① A 8.1 5.6 6.8 11.3 13.5 15.8 22.5 28.1 33.8 40.5 45.0 59.1 67.5 112.5
Heating capactiy② KW 9.0 15.0 18.0 30.0 36.0 42.0 60.0 75.0 90.0 108.0 120.0 150.0 180.0 300.0
BTU/h 30700 51200 61400 102400 122800 143300 204700 255900 307100 368500 409400 511800 614200 1023600
COP② W/W 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05
Input power (Heating)② KW 2.22 3.70 4.44 7.41 8.89 10.37 14.81 18.52 22.22 26.67 29.63 37.04 44.44 74.07
Input current (Heating)② A 10.1 7.0 8.4 14.1 16.9 19.7 28.1 35.2 42.2 50.6 56.3 70.3 84.4 140.7
Cooling capacity KW 7.8 13.0 15.6 26.0 31.2 36.4 50.0 65.0 75.0 90.0 100.0 120.0 150.0 250.0
BUT/h 26600 44400 53200 88700 106500 124200 170600 221800 255900 307100 341200 409400 511800 853000
Input power (Cooling) KW 1.86 3.08 3.70 6.17 7.32 8.60 11.90 15.29 17.80 21.40 23.80 28.24 35.70 59.50
Input current (Cooling) A 8.5 5.8 7.0 11.7 13.9 16.3 22.6 29.0 33.8 40.6 45.2 53.6 67.8 113.0
Power supply V/PH/Hz 220/1/50 380/3/50
Compressor   Rotary Scroll
Max running current A 14.5 10.1 12.2 20.3 24.3 28.4 40.5 50.7 60.8 72.9 81.0 101.3 121.6 202.6
Noise dB(A) 50 50 51 53 55 55 56 56 57 59 62 62 65 67
Water inlet/outlet inch 1″ 1″ 1″ 1-1/4″ 1-1/4″ 1-1/2″ 2″ 3″ 3″ 3″ 4″ 4″ 4″ 5″
Water flow volume (5~3℃difference) m³/h 1.7~2.6 2.8~4.3 3.3~5.2 5.5~8.6 6.6~10.3 7.7~12.0 11.0~17.2 13.8~21.5 16.5~25.7 19.8~30.9 22.0~34.4 28.9~43.0 33.0~51.6 55.0~86.0
Refrigerant R22/R410A/R407C
Unit dimension (L/M/H) mm 670/600/760 755/665/725 755/665/725 840/720/1160 840/720/1160 840/720/1160 1220/1100/1515 1220/1100/1515 1630/1100/1515 1630/1100/1515 2010/1100/1515 2010/1100/1515    
Shipping dimension (L/M/H) mm 720/650/860 805/715/825 805/715/825 890/770/1260 890/770/1260 890/770/1260 1290/1170/1715 1290/1170/1715 1750/1170/1715 1750/1170/1715 2130/1170/1715 2130/1170/1715    
Remark:
(1) Cooling: Air condition side  inlet/outlet: 12℃/7℃, Hot source side inlet/outlet:30℃/35℃
(2) ①Heating: Air condition side  inlet/outlet: 30℃/35℃, Hot source side inlet/outlet:10℃/-
(3) ②Heating: Air condition side  inlet/outlet: 40℃/45℃, Hot source side inlet/outlet:10℃/-
(4) Running temperature: Ambient temperature-30℃~50℃, Hot source water temperature 8℃~38℃